  1. Slide 1: Power for the Next Moment

    Slide 1: Power for the Next Moment

    POWER FOR THE NEXT MOMENT INNOVATION DAY // NOVEMBER 10, 2026 // AUSTIN, TEXAS

  2. Slide 2: Today's Agenda

    Slide 2: Today's Agenda

    TODAY’S AGENDA INTRODUCING FROM DIRT WINNING ACROSS UNLOCKING THE CLOSING REMARKS AXIOM TO TOKENS THE ARCHITECTURE POWER STORY Chris Butler Revathi Advaithi Chief Technology & Rob Campbell Kevin Krumm Revathi Advaithi Chief Executive Officer Strategy Officer Chief Commercial Officer Chief Financial

  3. Slide 3: Cautionary Statement Regarding Forward-Looking Statements and Non-GAAP Disclosures

    Slide 3: Cautionary Statement Regarding Forward-Looking Statements and Non-GAAP Disclosures

    Cautionary Statement Regarding Forward -Looking Statements and Non -GAAP Disclosures This presentation contains forward -looking statements within the meaning of Section 27A of the Securities Act of 1933, as amende d, and Section 21E of the Securities Exchange Act of 1934, as amended. Words such as

  4. Slide 4: Introducing Axiom

    Slide 4: Introducing Axiom

    SECTION 01 Introducing Axiom Revathi Advaithi Expected Chief Executive Officer

  5. Slide 5: Axiom at a glance

    Slide 5: Axiom at a glance

    Axiom at a glance REVENUE (CY26E) R&D + SERVICE MANUFACTURING END TO END PORTFOLIO LOCATIONS LOCATIONS ~$10B 8 19 EMPLOYEES ENGINEERS GLOBAL SCALE & POWER REACH COOLING COMPUTE ~35K ~5K ~11M ft² SERVICES 5

  6. Slide 6: A generational investment in infrastructure

    Slide 6: A generational investment in infrastructure

    A generational investment in infrastructure AI is bringing the digital and industrial worlds together. A MULTIYEAR AI POWER REQUIRED BY AI GRID INVESTMENT PLANNED INVESTMENT CYCLE 200+ $1T+ GW $1.4T Estimated average annual New power to be added for data US utility investment, 2026 to hyperscaler ca

  7. Slide 7: A new era of infrastructure demands a new approach

    Slide 7: A new era of infrastructure demands a new approach

    A new era of infrastructure demands a new approach THE NEW ERA OF DIGITAL THE TRADITIONAL MODEL AXIOM WAS BUILT TO AND ELECTRICAL WILL NOT SCALE LEAD IN THIS NEW ERA INFRASTRUCTURE ▪ The traditional industrial model ▪ We built Axiom to bring the digital ▪ AI is driving a step -change in the was buil

  8. Slide 8: A portfolio built for the new infrastructure model

    Slide 8: A portfolio built for the new infrastructure model

    A portfolio built for the new infrastructure model Leading capabilities across the full power, cooling and compute system 2017 Board power First rack level power 2nd hyperscale compute Added direct to chip Expanded capabilities acquired programs for / rack program ramps liquid cooling utility from E

  9. Slide 9: A distinctive set of products engineered to work together

    Slide 9: A distinctive set of products engineered to work together

    A distinctive set of products engineered to work together POWER CONVERSION PRODUCTS Inverters M Rack M System (Agile 800R) CRITICAL POWER PRODUCTS LV/MV Switchgear PDUs RPPs Busway Modular Utility Metering RACK & CHIP LEVEL POWER PRODUCTS Power modules Vertical power CBU Power shelf 800V sidecar COM

  10. Slide 10: Axiom can shape and deliver the system as one

    Slide 10: Axiom can shape and deliver the system as one

    Axiom can shape and deliver the system as one Power, Cooling, and Compute capabilities spanning utility interface through the AI workload We design the architecture, not just the products POWER CONVERSION Optimize the system, not just individual components EMBEDDED POWER We remove complexity from th

  11. Slide 11: Built on world-class manufacturing DNA, designed for the AI era

    Slide 11: Built on world-class manufacturing DNA, designed for the AI era

    Built on world -class manufacturing DNA, designed for the AI era Axiom combines the portfolio and technology required for the new infrastructure model with manufacturing scale and an AI -native operating system AI -NATIVE OPERATING MODEL ACROSS THE ENTERPRISE INTELLIGENT SYSTEMS REAL - TIME VISIBILI

  12. Slide 12: Axiom is fundamentally different from its peers

    Slide 12: Axiom is fundamentally different from its peers

    Axiom is fundamentally different from its peers WHAT MAKES IT HARDWARE INTEGRATORS AXIOM DIFFERENT Integrate compute at scale, with limited Designs, manufactures and integrates proprietary power or thermal product IP power, cooling and compute as one Purpose -built for the new system, across the ele

  13. Slide 13: Shaping infrastructure with our customers from utility to silicon

    Slide 13: Shaping infrastructure with our customers from utility to silicon

    Shaping infrastructure with our customers from utility to silicon UTILITIES COLOCATION HYPERSCALERS SILICON PROVIDERS Grid interconnection, Critical power distribution Integrated power, cooling Co -development of next - substation and utility and modular power and compute systems to generation power

  14. Slide 14: Leadership matched for the opportunity ahead

    Slide 14: Leadership matched for the opportunity ahead

    Leadership matched for the opportunity ahead Significant industry experience with track record of results YEARS AT YEARS AT YEARS AT YEARS AT YEARS AT 7 FLEX 2 FLEX 11 FLEX 9 FLEX 1 FLEX INDUSTRY INDUSTRY INDUSTRY INDUSTRY INDUSTRY 35 YEARS 30 YEARS 40 YEARS 15 YEARS 25 YEARS Prior Experience Prior

  15. Slide 15: From Dirt to Tokens

    Slide 15: From Dirt to Tokens

    SECTION 02 From Dirt to Tokens Chris Butler Expected Chief Technology & Strategy Officer

  16. Slide 16: AI is power-limited and the fastest from megawatts to tokens wins

    Slide 16: AI is power-limited and the fastest from megawatts to tokens wins

    AI is power -limited and the fastest from megawatts to tokens wins EFFICIENCY More compute from every megawatt the grid delivers. SIMPLIFICATION Fewer conversion stages, vendors and handoffs from grid to token. SPEED Capacity online in up to half the time. 16

  17. Slide 17: AI presents new customer challenges

    Slide 17: AI presents new customer challenges

    AI presents new customer challenges INCREASING RACK DENSITY Industry focused efforts towards 800V and liquid c ooling POWER AVAILABILITY Poor efficiency and long waits for interconnection INCREASING COMPLEXITY Density challenge is adding complexity LABOR CONSTRAINTS Shortage of skilled onsite resour

  18. Slide 18: AI presents new customer challenges

    Slide 18: AI presents new customer challenges

    AI presents new customer challenges INCREASING RACK DENSITY Industry focused efforts 800V and Liquid Cooling EFFICIENCY POWER AVAILABILITY Poor efficiency and long waits for interconnection SIMPLIFICATION INCREASING COMPLEXITY SPEED Density challenge is adding complexity LABOR CONSTRAINTS Shortage o

  19. Slide 19: 100+ years of AC. 3-5 years to DC.

    Slide 19: 100+ years of AC. 3-5 years to DC.

    100+ years of AC. 3 –5 years to DC. A century spent refining one architecture. AI is forcing a reset in a single product cycle. 1880s – 1900s 1920s – 1950s 1960s – 1980s 1980s – 2000s 1990s – 2010s 2010s – TODAY AC NETWORKS GRID SCADA AND SOLID -STATE UPS AND SMARTER AND SUBSTATIONS EXPANSION AUTOMA

  20. Slide 20: Incumbents protect the past. Axiom ships what's next

    Slide 20: Incumbents protect the past. Axiom ships what's next

    Incumbents protect the past. Axiom ships what’s next INDUSTRIAL INCUMBENTS The legacy AC playbook 800VDC -native, built for speed AC -centric portfolios: UPS, PDU and power 800VDC -native: agile digital rectifier, ARCHITECTURE racks — the very boxes 800VDC removes grid -forming SST, integrated backu

  21. Slide 21: The value of efficiency, speed, and simplification

    Slide 21: The value of efficiency, speed, and simplification

    The value of efficiency, speed, and simplification ~ $20 – $30B ~ $1.5– $2.5B compute lease revenue potential per GW / year of potential revenue lost per GW for every month of delay ~ $12 – $15B < 1 year to build the power and cooling infrastructure for 1 GW of potential revenue pays it back, so pay

  22. Slide 22: One grid to token platform

    Slide 22: One grid to token platform

    One grid to token platform MV AND LV SWITCHGEAR BUSWAY AND DATABAR AGILE AND GRID - FORMING BESS LIFECYCLE SERVICES PDUs AND RPPs PREFAB PODS AND SKIDS 800V DIGITAL RECTIFIERS SST (ROADMAP) ▪ Logistics and fulfillment ▪ Repair and refurbishment 01 CRITICAL POWER 02 POWER CONVERSION ▪ Remote monitori

  23. Slide 23: Critical power, set and connected on site

    Slide 23: Critical power, set and connected on site

    Critical power, set and connected on site MV & LV Busway & switchgear databar PDU & RPP Modular Protection and distribution Power and data run overhead Branch distribution and remote Utility control buildings and from the utility feed to the to every row power panels at the row power pods, built and

  24. Slide 24: Facility power conversion, built in-house

    Slide 24: Facility power conversion, built in-house

    Facility power conversion, built in -house Grid - forming BESS M - Rack Agile 800R ■ Next -gen ready Sets voltage and frequency and absorbs AI Liquid -cooled, modular grid -forming Digital rectifier with agile backup: 34.5 kV in, load swings in milliseconds inverter: SiC, >99% efficient, 5 –7.5 MW 8

  25. Slide 25: Few players control power inside the rack

    Slide 25: Few players control power inside the rack

    Few players control power inside the rack Power Power Sidecar shelf BBU CBU module ■ Leading player 800 VDC or ± 400 VDC 50 V rack distribution: Battery backup units on Capacitive storage that Board -level DC/DC and beside the rack, feeding 33 kW shelves at 97.5% the 50 V bus for ride - smooths AI l

  26. Slide 26: Cloud and cooling, commissioned before it ships

    Slide 26: Cloud and cooling, commissioned before it ships

    Cloud and cooling, commissioned before it ships Compute Fluid network CDU Cold Plate Integrated manufacturing: Facility -to-rack liquid Coolant distribution units Direct -to-chip cooling at the built, commissioned, piped, distribution, supply and return moving heat from rack to processor ■ Token -re

  27. Slide 27: One grid to token platform

    Slide 27: One grid to token platform

    One grid to token platform MV AND LV SWITCHGEAR BUSWAY AND DATABAR AGILE AND GRID - FORMING BESS LIFECYCLE SERVICES PDUs AND RPPs PREFAB PODS AND SKIDS 800V DIGITAL RECTIFIERS SST (ROADMAP) ▪ Logistics and fulfillment ▪ Repair and refurbishment 01 CRITICAL POWER 02 POWER CONVERSION ▪ Remote monitori

  28. Slide 28: One system, one owner, tuned for efficiency

    Slide 28: One system, one owner, tuned for efficiency

    One system, one owner, tuned for efficiency OUR PORTFOLIO CUSTOMER VALUE Power conversion EFFICIENCY MV · GRID - FORMING · 800VDC 80 MW+ unlocked per GW Power distribution AXIOM SYSTEM DESIGN SWITCHGEAR · BUSWAY · PDUS System efficiency SIMPLIFICATION Rack and board power at the core, everything des

  29. Slide 29: Today's power architecture, grid to token

    Slide 29: Today's power architecture, grid to token

    Today’s power architecture, grid to token Grid Chip Facility power train (AC) IT rack PSU Power shelf 480 →50 V MV switchgear Transformer LV switchgear UPS PDU Busway BBU BBU battery ride -through CBU CBU capacitive load smoothing Inside the server 13.8 –34.5 kV AC 480 VAC IBC VRM GPU 50 →12 V 12→0.

  30. Slide 30: Small losses at every stage add up to 20%

    Slide 30: Small losses at every stage add up to 20%

    Small losses at every stage add up to 20% Grid Chip IT rack Facility power train (AC) PSU Power shelf 480 →50 V 97.5% MV switchgear Transformer LV switchgear UPS PDU Busway BBU BBU battery ride -through 99.9% 98.5% 99.8% 96.0% 98.0% 99.6% CBU CBU capacitive load smoothing Inside the server 13.8 –34.

  31. Slide 31: Most players own only a slice of the chain

    Slide 31: Most players own only a slice of the chain

    Most players own only a slice of the chain Grid Chip Facility power train (AC) IT rack PSU Power shelf 480 →50 V MV switchgear Transformer LV switchgear UPS PDU Busway BBU BBU battery ride -through CBU CBU capacitive load smoothing Inside the server 13.8 –34.5 kV AC 480 VAC IBC VRM GPU 50 →12 V 12→0

  32. Slide 32: What the next architecture needs

    Slide 32: What the next architecture needs

    What the next architecture needs Grid Chip Facility power train (AC) IT rack PSU Power shelf 480 →50 V MV switchgear Transformer LV switchgear UPS PDU Busway BBU BBU battery ride -through CBU CBU capacitive load smoothing Inside the server 13.8 –34.5 kV AC 480 VAC IBC VRM GPU 50 →12 V 12→0.6 V 0.6 V

  33. Slide 33: A bridge step for today's VAC racks

    Slide 33: A bridge step for today's VAC racks

    A bridge step for today’s 480 VAC racks EFFICIENCY SIMPLIFICATION SPEED Axiom Agile 480 consolidates medium -voltage conversion and backup ahead of existing LV distribution Grid Chip TODAY ~92 % PSU BBU IBC VRM 480 → 50V CBU 50 →12V 12→0.6V to the rack MV switchgear Transformer LV switchgear UPS PDU

  34. Slide 34: One fault took >3GW off the grid

    Slide 34: One fault took >3GW off the grid

    One fault took >3GW off the grid Integrating the UPS into energy storage eliminates a top utility concern: sudden load drops. ILLUSTRATIVE VOLTAGE RESPONSE Milliseconds A single transmission fault >3GW Of data -center load switched to backup at the same moment >10min Of voltage disturbance, felt acr

  35. Slide 35: Grid-forming creates the grid

    Slide 35: Grid-forming creates the grid

    Grid -forming creates the grid A grid -forming inverter establishes and regulates AC voltage and frequency, so generation and loads can synchronize to it, rather than simply following the grid. Traditional Grid -forming grid -following ▪ Requires an existing voltage and frequency reference ▪ Creates

  36. Slide 36: A bridge step for today's VAC racks

    Slide 36: A bridge step for today's VAC racks

    A bridge step for today’s 480 VAC racks EFFICIENCY SIMPLIFICATION SPEED Axiom Agile 480 consolidates medium -voltage conversion and backup ahead of existing LV distribution TODAY ~92 % PSU BBU IBC VRM 480 → 50V CBU 50 →12V 12→0.6V to the rack MV switchgear Transformer LV switchgear UPS PDU Busway 6

  37. Slide 37: One system replaces the AC power chain

    Slide 37: One system replaces the AC power chain

    One system replaces the AC power chain EFFICIENCY SIMPLIFICATION SPEED Agile 800R: centralized conversion and backup at 97% efficiency Grid Chip TODAY ~92 % PSU BBU IBC VRM 480 → 50V CBU 50 →12V 12→0.6V to the rack MV switchgear Transformer LV switchgear UPS PDU Busway 6 stages to the rack 480VAC IT

  38. Slide 38: One system replaces the AC power chain

    Slide 38: One system replaces the AC power chain

    One system replaces the AC power chain EFFICIENCY SIMPLIFICATION SPEED Agile 800R: centralized conversion and backup at 97% efficiency Grid Chip TODAY ~92 % PSU BBU IBC VRM 480 → 50V CBU 50 →12V 12→0.6V to the rack MV switchgear Transformer LV switchgear UPS PDU Busway 6 stages to the rack 480VAC IT

  39. Slide 39: Transition to solid-state transformers

    Slide 39: Transition to solid-state transformers

    Transition to solid -state transformers EFFICIENCY SIMPLIFICATION Next -gen efficiency, compact footprint, integrated protection and control Grid Chip TODAY ~92 % PSU BBU IBC VRM 480 → 50V CBU 50 →12V 12→0.6V to the rack MV switchgear Transformer LV switchgear UPS PDU Busway 6 stages to the rack 480

  40. Slide 40: Improving efficiency in the rack

    Slide 40: Improving efficiency in the rack

    Improving efficiency in the rack Transition to 800V native servers and compute IT rack 800V Server PSU Power shelf 480 →50 V BBU BBU battery ride -through 800V PDB CBU CBU capacitive load smoothing VRM 800 →12V 12→0.6V Replaces PSU, BBU, and IBC Inside the server IBC VRM GPU 50 →12 V 12→0.6 V 0.6 V

  41. Slide 41: Improving efficiency in the rack

    Slide 41: Improving efficiency in the rack

    Improving efficiency in the rack Transition to 800V native servers and compute FIVE EFFICIENCY LEVERS IT rack ■ Regulation Allows fixed ratio converters @ 98% Regulate once, upstream. PSU Power shelf 480 →50 V ■ Isolation Isolate at one point only. Isolating twice costs 1 -2 points. BBU BBU battery

  42. Slide 42: Improving efficiency in the rack: 800V native servers and compute

    Slide 42: Improving efficiency in the rack: 800V native servers and compute

    Improving efficiency in the rack EFFICIENCY 800V native servers and compute TRADITIONAL THE STAGE THAT REPLACES IT 480VAC TO THE RACK 800V POWER DISTRIBUTION BOARD 85.7% 480VAC 95% 50VDC 97% 12V 93% 0.8V AXIOM 800VDC TO THE RACK 90.2% 800VDC Removed 97% 12V 93% 0.8V +4 pts 800VDC in, 12V out. Hot sw

  43. Slide 43: Improved efficiency and simplified architecture deliver real results

    Slide 43: Improved efficiency and simplified architecture deliver real results

    Improved efficiency and s implified EFFICIENCY SIMPLIFICATION SPEED architecture deliver real results Grid to rack Rack to chip Total, grid -to-chip × = 98%+ to the rack, from ~92% today 90% rack to chip, from 85.7% today 88% grid -to-chip, from ~80% today more revenue potential per GW per year for

  44. Slide 44: Long track record in modular power

    Slide 44: Long track record in modular power

    EFFICIENCY SIMPLIFICATION SPEED Long track record in modular power Factory -built power for datacenter and utility customers across the U.S. and Europe MV e -house Hyperscale power skid 4.16–38 kV switchgear, factory -tested Up to 36 kV, Level 3 tested MV and LV power distribution, built, wired and

  45. Slide 45: The AI Module accelerates the build timeline

    Slide 45: The AI Module accelerates the build timeline

    The AI Module accelerates the build timeline SIMPLIFICATION SPEED Power, cooling and compute built and tested in the factory while the site is prepared Stick -built Design Site and building Power and cooling Racks and integration Commissioning one trade after another AI MODULE Design Site prep site

  46. Slide 46: The Axiom Architecture Lab

    Slide 46: The Axiom Architecture Lab

    The Axiom Architecture Lab Where Axiom builds and validates the full architecture, grid to token, before it reaches a customer site 01 Build 02 Validate 03 Certify 04 Show Complete reference architectures: Power and thermal load testing, FMEA, UL and NVIDIA evaluation, Customers see the whole system

  47. Slide 47: More tokens from every megawatt, sooner

    Slide 47: More tokens from every megawatt, sooner

    More tokens from every megawatt, sooner One grid -to-token platform built around three outcomes EFFICIENCY SIMPLIFICATION SPEED More compute per megawatt One system, one owner Capacity online sooner ~8 pts One platform Up to 50% efficiency improvement, grid -to-chip conversion and agile backup in th

  48. Slide 48: Winning Across the Architecture

    Slide 48: Winning Across the Architecture

    SECTION 03 Winning Across the Architecture Rob Campbell Expected Chief Commercial Officer

  49. Slide 49: Driving growth through efficiency, simplification, and speed

    Slide 49: Driving growth through efficiency, simplification, and speed

    Driving growth through efficiency, simplification, and speed 01 02 03 Engage before the Expand across the Execute and scale architecture is set portfolio, programs and from products to systems generations We architect with customers early, Our portfolio breadth allows a single We deliver standalone

  50. Slide 50: High performance AI demands integrated design engagement

    Slide 50: High performance AI demands integrated design engagement

    High performance AI demands integrated design engagement Rising power density brings chip, rack, and facility decisions together TRADITIONAL MODEL LEADING HIGH -PERFORMANCE AI DEPLOYMENTS Separate decisions, staggered engagement Coordinated earlier across the architecture Chip power & Chip power & c

  51. Slide 51: The buildout is expanding our opportunity on two fronts

    Slide 51: The buildout is expanding our opportunity on two fronts

    The buildout is expanding our opportunity on two fronts Evolving power architectures increase content per MW, while growing AI deployments drive demand for custom compute POWER TODAY’S ARCHITECTURE CLOUD CUSTOM COMPUTE ~$2.8M / MW ~40 %+ Driven by rising rack densities & COOLING market CAGR through

  52. Slide 52: Our deepest customer relationships span the full portfolio

    Slide 52: Our deepest customer relationships span the full portfolio

    Our deepest customer relationships span the full portfolio Years of engagement across multiple businesses, programs and technology generations. Board - Rack -level Power Critical Liquid Compute Modular Services power power conversion Power cooling Hyperscaler 1 ● ● ● ● ● ○ ● ○ 30+ active programs Hy

  53. Slide 53: Product Showcase

    Slide 53: Product Showcase

    PRODUCT SHOWCASE Chris Butler, Rob Campbell, Todd Hoover, Mattias Jansson

  54. Slide 54: Unlocking the Power Story

    Slide 54: Unlocking the Power Story

    SECTION 04 Unlocking the Power Story Kevin Krumm Expected Chief Financial Officer

  55. Slide 55: Multiple growth drivers underpin 20%+ 3-yr. revenue CAGR

    Slide 55: Multiple growth drivers underpin 20%+ 3-yr. revenue CAGR

    Multiple growth drivers underpin 20%+ 3 -yr. revenue CAGR from CY27E to CY30E Strong end -market demand, secured capacity and next -generation architectures provide visibility to sustained growth 01 02 03 STRUCTURAL MARKET GROWTH SCALED CAPACITY AND EXECUTION CONTENT AND REVENUE VISIBILITY Expanding

  56. Slide 56: Scaling revenue and adjusted EBITDA margin through 2030

    Slide 56: Scaling revenue and adjusted EBITDA margin through 2030

    Scaling revenue and adjusted EBITDA margin through 2030 Strong growth and operating leverage translate into expanding margins and significant cash generation REVENUE GROWTH ADJUSTED EBITDA 01 REVENUE GROWTH 02 BY SEGMENT 03 MARGIN EXPANSION Drivers Drivers Drivers • Committed program ramps • Power f

  57. Slide 57: Path to 800V expands our power opportunity

    Slide 57: Path to 800V expands our power opportunity

    Path to 800V expands our power opportunity Existing products provide the foundation; 800V and new solutions drive growth through CY30 ILLUSTRATIVE POWER REVENUE OPPORTUNITY 40%+ 3-Yr. Revenue CAGR CY2 7E to CY30 E $6 – $6.3B ~$3.5B Revenue Revenue CY26E CY27E CY28E CY29E CY30E Existing portfolio 800

  58. Slide 58: Power mix shift supports adjusted EBITDA margin expansion

    Slide 58: Power mix shift supports adjusted EBITDA margin expansion

    Power mix shift supports adjusted EBITDA margin expansion A larger contribution from a higher -margin, expanding -margin Power business supports consolidated margin expansion. TOTAL ADJUSTED EBITDA CONTRIBUTION POWER | Adjusted EBITDA Margin Mix by segment CY26E CY27E CY 30 E POWER POWER High Teens

  59. Slide 59: Front-loaded growth investment drives strong cash generation

    Slide 59: Front-loaded growth investment drives strong cash generation

    Front -loaded growth investment drives strong cash generation Capital intensity moderates as capacity comes online, supporting 90%+ FCF conversion by CY2030E CAPITAL EXPENDITURES FREE CASH FLOW CONVERSION % OF REVENUE % OF ADJUSTED NET INCOME ~10% 90%+ ~6% ~40%+ ~3 -4% Negative CY26E CY27E CY2028E C

  60. Slide 60: Disciplined capital allocation prioritizes high-return growth

    Slide 60: Disciplined capital allocation prioritizes high-return growth

    Disciplined capital allocation prioritizes high -return growth Deploying capital to drive long -term value while targeting investment -grade metrics 01 02 03 ORGANIC GROWTH SELECTIVE M&A BALANCE SHEET FLEXIBILITY First priority for capital Extend products, technology and Target investment -grade met

  61. Slide 61: Strong balance sheet preserves strategic flexibility

    Slide 61: Strong balance sheet preserves strategic flexibility

    Strong balance sheet preserves strategic flexibility Investment -grade metrics and strong liquidity provide capacity to invest through the cycle ~$1.0B+ ~$2.4B ~$1.3B $2.0B CASH TERM DEBT 5 -YEAR REVOLVING PREFERRED CREDIT FACILITY (1) At separation 3- and 5 -yr. 6% cash or SOFR + 137.5 –150 bps 7%

  62. Slide 62: Financial framework and outlook

    Slide 62: Financial framework and outlook

    Financial framework and outlook CY2026 estimate, CY2027 outlook and CY2030 framework: Total Axiom CY26E CY27 OUTLOOK CY30E FRAMEWORK Revenue ~$9.7B $20 – $21B $37B+ (20%+ CY27E – CY30E CAGR) Power ~$3.5B $6 – $6.3B 40%+ CAGR Cloud & Cooling ~$6.2B $14 – $14.7B 10%+ CAGR Adjusted EBITDA Margin ~11% ~

  63. Slide 63: Peer benchmarking

    Slide 63: Peer benchmarking

    Peer benchmarking POWER CLOUD & COOLING POWER PEERS SPECIALIZED EMS PEERS Peers Power segment Cloud & Cooling segment CY27 Revenue ~76% (1) ~13% median ~131% (1) ~59% median Growth CY27 Adjusted EBITDA Mid-20s ~24% median HSD – LDD ~11% median Margin CY27 revenue growth: CY27E adj. EBITDA margin: CY

  64. Slide 64: Building the capabilities of an independent public company

    Slide 64: Building the capabilities of an independent public company

    Building the capabilities of an independent public company IT & FINANCE, TAX & RISK, LEGAL & LEADERSHIP & R&D / CYBERSECURITY CONTROLS COMPLIANCE GOVERNANCE INNOVATION ▪ Standalone ▪ SEC reporting and ▪ Insurance and ▪ Standalone ▪ Standalone applications and technical enterprise risk corporate func

  65. Slide 65: Q&A

    Slide 65: Q&A

    Q&A All Speakers Moderated by Michelle Simmons

  66. Slide 66: Axiom is built for the next moment

    Slide 66: Axiom is built for the next moment

    Axiom is built for the next moment Our portfolio and operating model set us apart and position us to outperform the market. THE RIGHT PRODUCT AND MANUFACTURING DNA + ATTRACTIVE FINANCIAL TECHNOLOGY AI -NATIVE OPERATIONS PROFILE PORTFOLIO ▪ Proven manufacturing and supply ▪ Outgrowing a rapidly expan

  67. Slide 67: Thank You

    Slide 67: Thank You

    HANK YOU axiom

Source: company website