Vector Limited · NZX:VCT
Vector — Technical Presentation (November 2011)
38 slides from Vector's technical presentation, November 2011

Slide 1: Physical Pipeline Modelling – Inputs and Assumptions
Physical Pipeline Modelling – Inputs and Assumptions Pipeline Capacity Consultation Presentation

Slide 2: Forum Agenda
9:30AM VENUES OPEN Tea, Coffee and Water provided 10:00AM INTRODUCTION Daniel McCarthy 10:15AM CHAIR INTRODUCTION AND HOUSEKEEPING Bruce Girdwood in Wellington Brenda Talacek in Auckland 10:25AM PRESENTATION – Q&A David Innes and Steve Kirkman 12:00PM/12:30PM LUNCH 1:00PM END OF FORMAL FORUM PROCEED

Slide 3: Consultation Process
Consultation Process Informed decision making by Vector 1. Modelling 2. Informed 3. Capacity Inputs and Modelling Determination Assumptions Greater transparency, wider understanding

Slide 4: Modelling Inputs and Assumptions
Modelling Inputs and Assumptions Modelling Assumptions Physical behaviour – capacity Simulated pipeline inputs determination (Part A) Model External inputs (Part B) Current Consultation

Slide 5: What do we mean by capacity?
What do we mean by capacity? The Model determines physical not commercial capacity Available capacity allows for: Forecast peak demand Maintenance of Systems Security Criteria Reasonable and Prudent operation of the Transmission System (RPO)

Slide 6: What do we mean by RPO?
What do we mean by RPO? Vector is required to operate the Transmission System under the Vector Transmission Code (VTC) as a Reasonable and Prudent Operator (RPO) RPO means: a standard of performance that is equal to or better than transmission system operating practice as determined by reference

Slide 7: Determining Pipeline Capacity
Determining Pipeline Capacity The Model determines physical capacity: the ability of a pipeline to meet a specific demand scenario To find the maximum capacity for a given scenario, load is increased incrementally at one (or more) Delivery Points until the minimum acceptable pressure occurs at s

Slide 8: Determining Pipeline Capacity (2)
Determining Pipeline Capacity (2) There may be numerous answers to the question of a pipeline’s capacity: eg, the capacity at: The last Delivery Point on the pipeline The Delivery Point with the highest daily, or annual, offtake Any combination of Delivery Points, simultaneously, etc, etc

Slide 9: Sample Model Output
Sample Model Output 8500.00 4 . : - - : 8000.00 f---- >e00.00 L-- — Rotowaro Kaui ; — Whangarei H H : : 7000.00 b----- — Westfield j 6500.00 6000.00 f Result Pressure(kPa) 5500.00 5000.00 }---- 4500.00 }---~ 4000.00, 2 0.0 1.00 2.00 3.00 f-===- 4.00 }--- 5.00 }---- 6.00 }---- 7.00 Time (days )

Slide 10: The Model
The Model The software uses “transient flow” analysis: Flow at most Delivery Points varies significantly over time, independently of flows at other points The Model allows scenarios to be analysed: Scenarios may be any combination of loads and/or physical configurations If the inputs to a

Slide 11: The Model (2)
The Model (2) The Model is actually a series of separate and separable “models”: North (= Rotowaro-north) Central North (= Rotowaro to Hamilton + Te Kowhai east) Central South (=Kapuni to Pokuru 2) Bay of Plenty Frankley Road to Kapuni South (= all pipelines south of Kapuni)

Slide 12: Model segments of the pipeline network
NORTH BAY OF PLENTY CENTRAL NORTH CENTRAL SOUTH FRANKLEY RD SOUTH

Slide 13: Impact of the Inputs
Impact of the Inputs These inputs have first order impact on available capacity: Pipeline diameter and length Achievable operating pressures Level and location of demand Inlet pressure Delivery pressures These inputs have second order impact on available capacity: Gas composition G

Slide 14: Physical Inputs
Physical Inputs Pipeline Sections: Pipelines are broken down into sections, between “nodes” Data for each section includes: Pipe length, outer diameter and wall thickness Altitude of each end The pipe roughness and efficiency factor Examples of nodes include: Receipt Points and Deliv

Slide 15: Physical Inputs (2)
Physical Inputs (2) Receipt Points may be set for flow control or pressure control: In most cases pressure control is used: flow is the variable Flow control is used where there is a known limit to the flow of gas (eg maximum output of a gas production station): pressure is the variable Deli

Slide 16: Physical Inputs (3)
Physical Inputs (3) Compression can be modelled in different ways: By defining the station in full detail, including all suction and discharge piping and valves, the physical parameters of each compressor unit (eg speed range, displaced volume, clearance ratio, capacity/head, rated power of the

Slide 17: External Inputs
External Inputs Gas Composition Actual compositions at the relevant Receipt Points are used The Model assumes the same gas composition applies throughout the relevant pipeline during a simulation This is a simplification, as gas composition varies over time The effect on capacity of variat

Slide 18: Line Pack
Line Pack Line Pack is the amount of gas in a pipeline at any given time Line pack is determined by pressures in a pipeline: if a load scenario satisfies minimum pressure requirements then line pack is sufficient

Slide 19: External Inputs: Loads
External Inputs: Loads Selection of the Peak Load Vector identifies the Monday – Friday period in which aggregate offtake from a pipeline is greatest (5-Day Peak) The whole week is then modelled to check that pressures recover sufficiently over the weekend

Slide 20: External Inputs: Loads (2)
External Inputs: Loads (2) The Base Case for modelling peak demand comprises: Distribution networks: flow profiles for the pipeline’s 5-Day Peak Plus, adjustment for organic growth and loads not included in the profile (if any) Direct-feed consumers: flow profiles for the pipeline’s 5-Day Pe

Slide 21: External Inputs: Loads (3)
External Inputs: Loads (3) Peak demand for distribution networks almost always occurs in winter Direct-feed consumers can be seasonal Power stations can ramp up to maximum at any time of year The 5-Day Peak varies year to year in both timing and size The peak day does not always occur in t

Slide 22: Example: Greater Auckland
Example: Greater Auckland Greater Auckland: Average Flow Rate in 5-Day Peak Total Bruce Maclaren Henderson Papakura Westfield Linear (Total) 16 Trend: y = 0.1889x - 366.45 14 12 Flow Rate, scm/s 10 8 6 4 2 0 01 02 03 04 05 06 07 08 09 10 11 20 20 20 20 20 20 20 20 20 20 20

Slide 23: Retail MDQ & Offtake, GJ/day
Retail MDQ & Offtake, GJ/day 1 O - ct ob 10,000 20,000 30,000 40,000 50,000 60,000 70,000 15 O er c 29 to be O r 12 cto N b ov er 26 e m N b ov er 10 e m D b ec er 24 e m D b ec er em 7 b Ja er n 21 uar Ja y nu 4 a Auckland Zone O/T Fe ry br 18 ua Fe ry br ua 4 ry M a 18 rch M ar ch 1 Ap r Auckland

Slide 24: Rotowaro-north Capacity Entitlements
Rotowaro-north Capacity Entitlements Rotowaro-north pipeline: Firm Transmission Capacity on 09/09/2011 Retail C apacity (Auckland Zone) 33% Total 176 TJ/day Power Stations 56% Retail C apacity (excl. Auckland) 11%

Slide 25: Minimum Acceptable Pressure
Minimum Acceptable Pressure Pressures determined by the Model must satisfy System Security Criteria Except as otherwise contracted, minimum pipeline pressures must be consistent with Schedule 1 of the Critical Contingency Management (CCM) Regulations Allowance is made for the time required to

Slide 26: High Contracted Delivery Pressures
High Contracted Delivery Pressures Consumer Nominal Delivery Pressure (bar g) Otahuhu B Nominal 48 Southdown Minimum 49 Te Rapa Cogeneration Plant Nominal 22.5 Taranaki Combined-Cycle Nominal 31

Slide 27: Sample Model Output
Sample Model Output 8500.00 4 . : - - : 8000.00 f---- >e00.00 L-- — Rotowaro Kaui ; — Whangarei H H : : 7000.00 b----- — Westfield j 6500.00 6000.00 f Result Pressure(kPa) 5500.00 5000.00 }---- 4500.00 }---~ 4000.00, 2 0.0 1.00 2.00 3.00 f-===- 4.00 }--- 5.00 }---- 6.00 }---- 7.00 Time (days )

Slide 28: Economic Design Standard
Economic Design Standard It is not feasible to provide unlimited capacity Pipelines need to be designed for some peak load An economic design standard should be set Designing for a 1 in 20-year peak demand is not uncommon An economic design standard could result in peak time rationing in s

Slide 29: Are there any Questions?
Vector (7 Are there any Questions?

Slide 30: Consultation Indicative Timelines
Consultation Indicative Timelines WHAT WHEN DISCUSSION PAPERS: RELEASED: 7 NOVEMBER 2011 Physical Modelling Inputs Discussion Paper Vector as a Reasonable and Prudent Operator RESPONSES TO THE SUBMISSIONS: RELEASED: 7 NOVEMBER 2011 On the Pipeline Capacity Consultation Paper FIRST CONSULTATION FORUM

Slide 31: Final House Keeping - Reminders
Final House Keeping - Reminders Submissions are due as word documents by Close of Business (5PM) Friday 2 December Any confidential information should be provided in a separately marked copy (in other words please send two clearly marked copies) All submissions not marked confidential will be

Slide 32: Thank You for Participation
Vector 7 THANK YOU FOR PARTICIPATION

Slide 33: Supplementary Slides: Compression
Supplementary Slides Compression

Slide 34: Pressure and Compression
Pressure and Compression Gas flows in a pipeline in response to a pressure gradient Pressure gradients arise whenever gas is taken at Delivery Points: the more gas taken, the steeper the gradient and the greater the flow A compressor increases flow by “steepening” the pressure gradient, while

Slide 35: Compression Capacity Checking
Compression Capacity Checking If compression is represented by a fixed discharge pressure, “real” compressors are not actually modelled It may then be necessary to check that the required flow does not exceed the capacity of the relevant compression, ie: the maximum flow rate at the compressor

Slide 36: Compression Capacity Checking
Compression Capacity Checking Vector’s North and BOP pipelines require an inlet pressure much higher than that available from the Maui Pipeline Maui Pipeline pressure may vary significantly, depending on whether Mokau compressor station is operating or not Mokau is operated according to the re

Slide 37: Rotowaro: Capacity vs Suction Pressure
Rotowaro: Capacity vs Suction Pressure Unit Type Rated Flow/Unit @ Suction Pressure: 30 bar g 35 bar g 40 bar g 45 bar g 50 bar g 3&4 Reciprocating scm/s 8 10 12 15 18 TJ/day 28 35 41 52 62 5&6 Centrifugal scm/s 44 50 58 64 TJ/day 152 173 200 221

Slide 38: Kapuni & Pokuru Compression Capacity
Kapuni & Pokuru Compression Capacity Compression at Kapuni consists of 3 reciprocating units: They receive gas from 300 Line and/or the KGTP Suction pressure is controlled (removing it as a variable) Deliverability is ~80 TJ/day while preserving n-1 redundancy Compression at Pokuru consist
Source: Internet Archive copy of vector.co.nz
More decks from Vector Limited
FY2026 Earnings Presentation22 slides · Aug 18, 2026
H1 FY2026 Earnings Presentation22 slides · Feb 20, 2026
Shareholder Meeting (September 2025)33 slides · Sep 30, 2025
FY2025 Earnings Presentation22 slides · Aug 25, 2025
H1 FY2025 Earnings Presentation22 slides · Feb 26, 2025
Shareholder Meeting (September 2024)29 slides · Sep 26, 2024