Vaisala Oyj Class A · OMXHEX:VAIAS
Vaisala Oyj Class A — Technical Presentation (April 2018)
44 slides from Vaisala Oyj Class A's technical presentation, April 2018
Slide 1: Online DGA-monitoring of power transformers
Online DGA-monitoring of power transformers Senja Leivo Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 © Vaisala
Slide 2: Webinar content
Webinar content 1. Dissolved gases – why and which gases 2. Fault types 3. Online monitoring – why 4. Things to consider when choosing a monitor 5. IR technology in online DGA – Vaisala Optimus™ DGA monitor 6. How to define limit values and interpret the data 7. How to utilize the online data – exam
Slide 3: Dissolved Gas Analysis
Dissolved Gas Analysis DGA is a comprehensive transformer condition assessment tool It can detect multiple fault types inside a transformer. Senja Leivo 2018-04-03 © Vaisala 3
Slide 4: Why gases form in a transformer?
Why gases form in a transformer? Chemical reactions happen when conditions favor them e.g. in presence of fuel, oxygen, heat and catalysts. Oil In case of a fault, temperature increase at fault location. Paper Copper WHY GASES: oil and/or paper decomposition due to thermal stresses gases form He
Slide 5: Which gases?
Which gases? 7 formed gases are commonly considered as key fault gases. Mathane, ethane, ethylene, acetylene, carbon monoxide, carbon dioxide and hydrogen (CH4, C2H6, C2H4, C2H2, CO, CO2 and H2) Which gases form depends on temperature at fault location materials in contact with the fault a
Slide 6: Fault types
Fault types PD partial discharge T1 thermal fault <300°C T2 thermal fault 300-700°C T3 thermal fault >700°C D1 Low energy discharge (sparking) D2 High energy discharge (arching) S Stray gassing of oil < 200 °C O Overheating < 250 °C C Carbonization of paper > 300 °C Most severe thermal faults wh
Slide 7: Why online monitoring
Why online monitoring © Vaisala
Slide 8: Why online DGA monitoring?
Why online DGA monitoring? 1. Online monitoring detects faults at their early phase Enables corrective actions before severe transformer failure. Cost reduction in maintenance and repair Avoid consequential costs of catastrophic failures. 2. Enables safe use of a transformer at its end-of-life
Slide 9: Why online DGA monitoring?
Why online DGA monitoring? “On-line monitors are particularly useful for applications where gas formation in electrical equipment must be followed at frequent time intervals (e.g., in strategic or expensive equipment, or where significant faults have already been detected). / Cigre TB409 WG D1.01
Slide 10: Why multi-gas online monitoring
Why multi-gas online monitoring “Worldwide experiences using on-line DGA increasingly show that all types of faults − thermal, low-energy discharge, high-energy discharge, and partial discharge − can be identified at an early stage. Identifying type and severity of a developing fault makes timely
Slide 11: Why multi-gas online monitoring
Why multi-gas online monitoring Often hydrogen monitors are used as early warning devices. However, not all faults produce significant amount of hydrogen. PD partial discharge, corona type T1 thermal fault <300°C T2 thermal fault 300-700°C T3 thermal fault >700°C D1 Low energy discharge (sparking)
Slide 12: Why multi-gas online monitoring
Why multi-gas online monitoring Continuous monitoring of key fault gases gives early and immediate notification of developing faults that may lead to transformer failure. Many failures can be prevented through real-time correlation of DGA data to e.g. load and oil/winding temperature. Only com
Slide 13: Things to consider when choosing a monitor
Things to consider when choosing a monitor © Vaisala
Slide 14: DGA monitors - what is relevant for the user?
DGA monitors - what is relevant for the user? No monitoring of monitors! No false alarms. Maintenance needs. No leaks. Robust design. Stable long-term measurement for gas trending. Easy to install. Tolerates all climate conditions. Senja Leivo 2018-04-03 © Vaisala 14
Slide 15: Lifetime costs
Lifetime costs Concerning the overall costs of a monitor, it’s not only the price of the instrument to be considered, +20% but also the costs associated with the installation and operation in service over its whole lifetime. Total cost of ownership to be considered when selecting a monitor. Senj
Slide 16: IR technology in online DGA - Vaisala Optimus DGA monitor
IR technology in online DGA - Vaisala Optimus™ DGA monitor © Vaisala
Slide 17: Infrared absorption (IR)
Infrared absorption (IR) IR is a fundamental analysis method, where light is absorbed by gas molecules. Gases have a unique absorption fingerprint which is used to identify gases present. Absorbed light intensity is proportional to number of gas molecules present in known gas volume. Gas spe
Slide 18: Infrared (IR) absorption by different DGA gases
Infrared (IR) absorption by different DGA gases Senja Leivo 2018-04-03 © Vaisala 18
Slide 19: Infrared technology, operating principle
Infrared technology, operating principle Gas molecules absorb infrared light when exposed to it. More molecules in the gas volume stronger absorption. Measured gas can be selected by changing the wavelength of the light with band-pass filters(s). IR cannot be used to measure gases like H2,
Slide 20: Difference in NDIR Technologies
Difference in NDIR Technologies (NDIR = non-dispersive infra red) Senja Leivo 2018-04-03 © Vaisala 20
Slide 21: Gas solubility vs gas extraction
Gas solubility vs gas extraction How well a gas dissolves into oil depends on: Oil type Temperature Total gas pressure in oil Gas composition in oil Gas solubility in oil is defined as Ostwald. Higher value more difficult to extract the gas from oil. Lower value the easier gas “e
Slide 22: Gas extraction methods
Gas extraction methods Methods to extract gas from oil** Naphthenic Paraffinic Toppler ~100% efficiency Oil density 0.864 0.849 Partial vacuum, 90-99% efficiency H2 0.074 0.036 Head space <30% efficiency O2 0.17 0.18 – Varies by gas type due to Ostwald coefficients and N2 0.11 0.12 gas to li
Slide 23: Partial vacuum gas extraction
Partial vacuum gas extraction Vaisala’s monitor uses unique vacuum extraction of gases. No vacuum pump used, oil column as piston. Magnetic gear pump Can extract >95% of the gases in oil. less dependent on gas gas solubility values Magnetic gear pump Senja Leivo 2018-04-03 © Vaisala 23
Slide 24: Vaisala solutions to prevent long-term drift
Vaisala solutions to prevent long-term drift Drift mechanism Vacuum Tunable Auto- Optics Hermetic IR- filter calibration vacuum Structure reference clean + temperature Light source Ѵ Filter transmission Ѵ Detector Ѵ Contamination Ѵ Ѵ Ѵ Cross-sensitivity Ѵ Ѵ Ѵ Senja Leivo 2018-04-03 © Vaisala 24
Slide 25: How to define limit values and interpret the data
How to define limit values and interpret the data © Vaisala
Slide 26: How to define alarm limits?
How to define alarm limits? 1. Comparing to values from standards – If no other reference is available. 2. Gas trending and gas ratios. 3. Using specific typical values per transformer family. Senja Leivo 2018-04-03 © Vaisala 26
Slide 27: Comparing values to standards
Comparing values to standards Typical gas concentration values (ppm) observed in power transformers. Data collected from about 25 electrical networks worldwide and including more than 20 000 transformers (IEC60599 Ed. 2.1 2007): Typical rate of gas increase (ppm/year): Senja Leivo 2018-04-03 © V
Slide 28: Comparing to values from standards
Comparing to values from standards Four-Condition DGA Guide (IEEE C57-104) Senja Leivo 2018-04-03 © Vaisala 28
Slide 29: Gas trending
Gas trending 2011-2015 Senja Leivo 2018-04-03 © Vaisala 29
Slide 30: Duval triangles
H2 CO CO2 CH4 C2H4 C2H6 C2H2 Duval triangles 216 237 3657 336 372 100 1.5 PD T1 T3 C T3 Triangle 1 Triangle 5 Senja Leivo 2018-04-03 © Vaisala 30
Slide 31: Duval triangles
Duval triangles High temperature fault T3, PD with possible T1 carbonization of paper. T3 C T3 Triangle 1 Triangle 5 Senja Leivo 2018-04-03 © Vaisala 31
Slide 32: PD T1 T3
PD T1 T3 C T3 Senja Leivo 2018-04-03 © Vaisala 32
Slide 33: Using typical values per transformer family
Using typical values per transformer family Using typical values per transformer family/design of utility’s own fleet. Comparing gas levels and gas RoC of those transformers. Transformer H2 CO CO2 CH4 C2H4 C2H6 C2H2 GSU1 23.9 260 1752 16.5 1.8 4.2 0 Useful especially when transformers GSU2 23.
Slide 34: Using typical values per transformer family
Using typical values per transformer family Transformer H2 CO CO2 CH4 C2H4 C2H6 C2H2 GSU1 23.9 260 1752 16.5 1.8 4.2 0 GSU2 23.3 301 1854 165.5 228.8 97.1 0 GSU3 16.1 357 2316 21.9 8.7 6.1 0 GSU4 28.2 238 1636 18.7 2.5 5.7 0 GSU5 27 499 2845 18.4 2.5 6.1 0 GSU6 42.3 739 3431 19 2.5 4.7 0 Senja Leivo
Slide 35: Utilizing online DGA data - examples
Utilizing online DGA data - examples © Vaisala
Slide 36: Review data against transformer temperature
Review data against transformer temperature Senja Leivo 2018-04-03 © Vaisala 36
Slide 37: Review data against transformer loading
Review data against transformer loading Senja Leivo 2018-04-03 © Vaisala 37
Slide 38: Use of information
Use of information If transformer generates gases only during loading peaks or exceptionally high temperature, this information can be used in local loading guidance or as input to more ? efficient cooling. If gas formation does not indicate severe fault, maintenance actions can be scheduled fur
Slide 39: How to compare online data and laboratory results
How to compare online data and laboratory results © Vaisala
Slide 40: Accuracy considerations
Accuracy considerations “For all methods operating on the headspace principle, a good knowledge of Ostwald or solubility coefficients K is required at all temperatures of gas extraction, in order to calculate gas concentrations in oil (monitor readings) from gas concentrations in the gas phase (ac
Slide 41: Laboratory accuracy, in percentage of the nominal value
Laboratory accuracy, in percentage of the nominal value Extraction procedure Medium Low concentration concentration Toepler 13 35 Partial degassing 13 30 Stripping 18 23 Headspace 18 37 Mercury-free Toepler 15* 14* Mercury-free partial degassing 11* Shake test 15 44 * Based on a limited number of an
Slide 42: Laboratory points with ±15% uncertainty bars
Laboratory points with ±15% uncertainty bars. Vaisala OPT100 graph ±10%. Laboratory: Located at power plant. Oil analysis within hours. Lab technician takes oil samples. Senja Leivo 2018-04-03 © Vaisala 42
Slide 43: Laboratory points with ±15% uncertainty bars
Laboratory points with ±15% uncertainty bars. Vaisala OPT100 graph ±10%. Senja Leivo 2018-04-03 © Vaisala 43
Slide 44: Thank you for joining the webinar.
Thank you for joining the webinar. Senja Leivo 2018-04-03 © Vaisala 44