  1. Slide 1: Model 560 Current Transformer

    Grid Solutions MODEL 560 Current Transformer Window Size 3.25” x 4.25” Application Insulation System Metering. Temperature Class H (180°C). Frequency Continuous Thermal Current Rating Factor 50-400 Hz. 1.33 at 30°C. amb., 1.0 at 55°C. amb. Terminals are brass studs No. 10-32 with one flatwasher, Ins

  2. Slide 2: Model 560 (cont'd)

    Model 560 (cont’d) ANSI METERING CLASS AT 60 Hz SECONDARY CATALOG CURRENT WINDING NUMBER RATIO RESISTANCE B0.1 B0.2 B0.5 B0.9 B1.8 (Ω @ 75°C) 560–152 1,500:5 * 0.3 0.3 0.3 0.3 0.6 0.368 560–162 1,600:5 * 0.3 0.3 0.3 0.3 0.6 0.262 560–202 2,000:5 * 0.3 0.3 0.3 0.3 0.6 0.328 560–252 2,500:5 * 0.3 0.3