  1. Slide 1: CME1056 Modular Cuber Technical Training

    CME1056 Modular Cuber Technical Training

  2. Slide 2: CME1056

    CME1056 • Product Information • Installation Details • Operation • Maintenance • Service Diagnosis

  3. Slide 3: CME1056 Modular Cuber

    CME1056 Modular Cuber • 30” wide by 24” deep platform • Replaces CME1002 and CME1000 – Air Cooled - Louvered Side Panels – Water Cooled - No louvers – Remote Air Cooled - No louvers • Remote uses ERC311 condenser

  4. Slide 4: CME1056 Modular Cuber

    CME1056 Modular Cuber • CM3 Technology – AutoIQ Controller – Adaptive Harvest – No seasonal adjustments – Automatic restarts

  5. Slide 5: Installation

    Installation • The Recipe for Ice has 3 ingredients: – Electricity – Water – Refrigeration • When properly mixed together by the ice machine, the bin fills with ice. If one or more of the ingredients is shorted, performance will suffer!

  6. Slide 6: Installation

    Installation • Fits all Scotsman 30” wide bins • Fits competitive 30” wide bins – Baffle needed • Fits Scotsman Bins – BH800 with Bin Top KBT23 – BH900 with Bin Top KBT22 • Fits many 30” wide Ice & Beverage Dispensers

  7. Slide 7: Installation: Water

    Installation: Water • Supply cold, potable 3/8” male flare water. water inlet • Connect rigid tubing to drain fitting and VENT it. – 12” standpipe 3/4” FPT drain fitting, do not overheat!

  8. Slide 8: Installation: Electricity

    Installation: Electricity • Electrical junction box in back panel – External 4 x 4 extension box can be added to Remotes or – Use standard internal junction box • Supply proper power – Check the nameplate!

  9. Slide 9: Installation: Refrigeration

    Installation: Refrigeration • Air Cooled – Need cool air supply • Baffle included for in- corner installations • Reduces hot air re- circulation Attach baffle to back corner.

  10. Slide 10: Installation: Remote

    Installation: Remote hd= hd horizontal distance rd= rise distance x 1.7 rd dd= drop distance x 6.6 hd+rd+dd=total Total <= 150 Total Drop dd Cannot Exceed 15 feet

  11. Slide 11: Installation: Remote

    Installation: Remote • Best Practices: – Condenser ABOVE ice machine – Shortest distance possible between condenser and ice machine – Control excess tubing

  12. Slide 12: Installation: Remote

    Installation: Remote • CME1056R uses ERC311 remote condenser – Headmaster in the condenser – RCKCME6GX headmaster kit must be added to McDonald’s installations when using their MAC condenser

  13. Slide 13: Installations: Water Cooled

    Installations: Water Cooled Condenser Water Inlet Condenser Drain

  14. Slide 14: Installation: Bin Thermostat

    Installation: Bin Thermostat • Route Thermostat Bulb through routing hole Thermostat Routing Hole Bulb

  15. Slide 15: Installation: Thermostat

    Installation: Thermostat Bottom View Bulb Bracket Mounting Holes Routing Hole Bracket

  16. Slide 16: Installation: Stacking

    Installation: Stacking • Can only stack with another CME1056 • Stacking kit – Includes curtain, hanger, gasket and Ice Drop Zone wire harness – Remove cascading shield from lower unit Curtain Hanger Bottom Unit

  17. Slide 17: Component Location

    Component Location Electrical Box Refrigeration System Access Freezing Valves Compartment Inlet Water Solenoid Valve Controller Purge Valve Pump Reservoir

  18. Slide 18: Cascading Shield

    Cascading Shield Ice Sensor Cascading Shield Water Trough Cascading Shield Snapped Over Ice Sensors Tab of Ice Sensor Cube Deflector and Cascading Shield Removed - Trough Still on Back Plate

  19. Slide 19: Controller

    Controller • Similar to CME1356 – Purge Valve System – Remote has Harvest Bypass Valve System

  20. Slide 20: Temperature Sensors

    Temperature Sensors • Water Temp Sensor – Only used for diagnostics – Confirms if system is refrigerating the water • There’s also a Discharge Temp Sensor Pump Water Temp Sensor Hose

  21. Slide 21: Initial Start Up

    Initial Start Up • Turn on the water Liquid Line Valve • Switch on the power • Air and Water Cooled: – Push Freeze • Remote: – Wait 4 hours and open the liquid line valve – Push Freeze Low Side Access

  22. Slide 22: Operation: Beginning Freeze

    Operation: Beginning Freeze • Purge Valve Opens for a short time then closes • Water Valve Opens, fills reservoir • When reservoir is full, compressor starts

  23. Slide 23: Operation: Water Control

    Operation: Water Control Upper Sensor • Water Level Sensor – Two infrared sensors • Bottom one indicates reservoir full when blocked • Top one indicates reservoir needs water OR to terminate freeze when it is blocked Lower Sensor

  24. Slide 24: Fan Control

    Fan Control • Air Cooled Fan Motor – Powered from Controller • Shuts off before Harvest • Off during Harvest • Cycles on & off during Freeze if discharge temp is low (<125oF.) • Remote Fan Motor – Powered by Contactor • Fan is On whenever Compressor is On

  25. Slide 25: Water Sequence: Freeze

    Water Sequence: Freeze • Water level determines length of freeze cycle/cube size – Water reservoir tops off at the beginning of freeze – Water reservoir fills once more during freeze – The second time the top sensor is blocked stops the freeze cycle

  26. Slide 26: Water Level Sensor

    Water Level Sensor • The controller uses the water level sensor to sense Upper Eye changes in water quantity – Upper electric eye indicates when water falls Lower Eye – Lower electric eye indicates when water rises

  27. Slide 27: Harvest Cycle

    Harvest Cycle • First harvest after any restart – 5 minutes long to establish a base line • All harvests – Pump stops – Hot gas valve opens – Purge valve timer energized • Purge valve opens for 40 seconds • Nothing draining - pump is OFF

  28. Slide 28: Harvest Cycle

    Harvest Cycle • Remotes open their Harvest Bypass Valve for a few seconds – Time varies depending upon discharge temperature, • Colder discharge = more valve open time • All Models: Pump restarts, water drains, purge valve closes – Inlet water valve opens for 9 seconds • Only for harvest assistance,

  29. Slide 29: Ice Sensing / Harvest Control

    Ice Sensing / Harvest Control Harvest Begins Harvest Ends Total Current Harvest Cycle Time (prior cycle actual + a % of actual) Actual Time to Release Ice Percent of Actual (prior cycle) Last Cube Fell Harvest Harvest Began Ended

  30. Slide 30: End of Harvest

    End of Harvest • Time expired – Either the unit returns to freeze or – It shuts off on Bin Full - when the bin thermostat contacts are closed – If ice was not “seen” by the ice sensors • Will make one more cycle • If it happens again, the unit shuts down • Will automatically restart for another try

  31. Slide 31: Ice and Evaporators

    Ice and Evaporators • Ice Formation – Refrigerant enters the evaporators at the top Inlets Cubes form at top first Ice Harvests in vertical strips Strips break when impacting the cube deflector

  32. Slide 32: Remote Operation

    Remote Operation Liquid Line • CME1056R uses Check Valve Bypass check valve and Valve bypass valve system – Headmaster in condenser Valve Strainer Discharge Check Valve

  33. Slide 33: Slide 33

  34. Slide 34: Remote Operation

    Remote Operation • Discharge line check valve seals off condenser during harvest – Isolates charge Discharge Line Check Valve

  35. Slide 35: Harvest Bypass Valve

    Harvest Bypass Valve • Opens a path between condenser and low side during harvest to meter in just enough refrigerant Harvest Bypass Valve

  36. Slide 36: Liquid Line Check Valve

    Liquid Line Check Valve • Prevents liquid migration to condenser during OFF cycle Liquid Line Check Valve

  37. Slide 37: Liquid Line Access Valve

    Liquid Line Access Valve • Controls liquid flow out of the receiver – Use allows two point recovery from the front of the machine • From low side • From liquid side – Liquid flow direction is same as freeze - check valves are open

  38. Slide 38: Liquid Line Access Valve

    Liquid Line Access Valve – An attached gauge will show Liquid Pressure • Connection is between Receiver and Heat Exchanger • Gauge reading is accurate during Freeze, but not Harvest – Discharge line check valve separates condenser – Gauge pressure in Harvest reads too high • Discharge pressure readi

  39. Slide 39: Restarts

    Restarts • Electrical Power Interruption – Automatic restart • Open the hot gas valve for 20 seconds • Open the purge valve • Start the pump • Shut the purge valve • Fill the reservoir • Start the compressor, freeze for 30 seconds • Harvest for 6 minutes

  40. Slide 40: Restarts

    Restarts • Water supply interruption – Automatic shut off and restart • Shuts off when float does not rise enough during water fill • Controller checks for water by opening the inlet water valve every 20 minutes – Will restart when the float rises far enough to break the bottom beam in the water lev

  41. Slide 41: Purge Adjustment

    Purge Adjustment • There are 5 levels – Maximum – Heavy – Standard - the factory setting – Moderate – Minimum • Number of green lights indicates purge level

  42. Slide 42: Cleaning and Sanitation

    Cleaning and Sanitation Push Harvest to release any ice and warm up the evaporators Push Clean and add 24 ounces of Scotsman Ice Machine Cleaner After 10 minutes push Clean again to flush out the Cleaner After 20 minutes push Off to stop

  43. Slide 43: Water Distributors

    Water Distributors Remove Water Distributors and Check Them - All Ports Must Be Open Evaporator Channels Must Be Open

  44. Slide 44: Air Cooled Service

    Air Cooled Service • Change Air Filters – Disposable – 20 x 20 x 1 – One on each side

  45. Slide 45: Split Fan Shroud

    Split Fan Shroud 1/4 turn fastener 1/4 turn fastener

  46. Slide 46: Fan Motor Service

    Fan Motor Service Loosen Bracket Loosen Bracket Set Screw

  47. Slide 47: Service Diagnosis

    Service Diagnosis • No ice, machine is off – Check the controller for lights • No lights = no power to controller – Check for power to machine – Check for transformer output

  48. Slide 48: Service Diagnosis

    Service Diagnosis • If there are lights - which ones are on? – Off light means the machine was switched off by someone – A Diagnostic light means a machine malfunction – Bin Full light means something has triggered either • the bin thermostat (closed) or • the ice sensors are blocked

  49. Slide 49: Service Diagnosis

    Service Diagnosis • Water Diagnostic Light – Blinks once and repeats • Water pump may not be working – Blinks twice and repeats • Water flow into machine too slow – Is ON without blinking • Inlet water valve leaking thru rapidly – If both the Water AND Refrigeration lights are on, check the thermist

  50. Slide 50: Water Sensor Diagnostics

    Water Sensor Diagnostics Power Water Fill Freeze Termination Ground or Negative

  51. Slide 51: Clean Water Sensor Lenses

    Clean Water Sensor Lenses Lenses Wipe lenses clean with a cotton swab - NOT A SCREWDRIVER!

  52. Slide 52: Service Diagnosis

    Service Diagnosis • Refrigeration Light – Blinks once and repeats • Ice release very slow, took maximum length harvest – Blinks twice and repeats • No ice sensed during maximum length harvest – Blinks three times and repeats • High discharge temperature

  53. Slide 53: Service Diagnosis

    Service Diagnosis • Refrigeration Light – Is ON without blinking • Low discharge temperature OR • Maximum length freeze cycle OR • Water cooled or remote may have cut out on high discharge pressure – Control resets automatically, but the controller may have timed out, depending upon when in the free

  54. Slide 54: Service Diagnosis

    Service Diagnosis • Bin Full light is ON – Bin may be full – 4 minute delay – Thermostat may be closed - is bin very cold? – Ice sensors may be blocked • Could need cleaning

  55. Slide 55: Scale on Ice Sensors

    Scale on Ice Sensors I worked until I got this dirty. Clean Me!

  56. Slide 56: Removal of Sensors

    Removal of Sensors • Remove cascading shield – Used on all two evaporator models • Reach in and twist cascading shield’s top forward to release it from its snap-on mounts • Push-pull sensors out of the machine

  57. Slide 57: Cleaning Sensors

    Cleaning Sensors • Clean sensors – Two types - tunnel mounted and module mounted – Eyes either in the back of the tunnel or on the module – Clean both with cotton swab or soft cloth Tunnel Type Module Mounted

  58. Slide 58: Cleaning Sensors

    Cleaning Sensors Clean Eyes Check Wire Remove Module Reassemble

  59. Slide 59: Ice Sensors

    Ice Sensors Clean Sensor Lenses with old soft toothbrush, NOT A SCREWDRIVER! Lens Ugly and Dirty! Clean Me! Good to Go! Note: Wet parts may appear clean, dry them to check.

  60. Slide 60: Service Diagnosis

    Service Diagnosis • Unit is running but both Diagnostic lights are ON – Check if temperature sensor (thermistor) set is plugged Temperature into the controller Sensor – If it is, replace the Connection temperature sensor set – Thermistors can also be checked by putting either probe in ice water • 32

  61. Slide 61: Refrigeration Diagnostics

    Refrigeration Diagnostics • Normal Cycle Time – 15 to 17 minutes at 70/50 – 16 to 19 minutes at 90/70 • Longer than normal times can be caused by – Dirty condenser – Low charge – Leaky inlet water valve – Inefficient compressor

  62. Slide 62: Refrigeration Diagnostics

    Refrigeration Diagnostics • Low Charge - Air or Water Cooled – Check by measuring suction line temperature at TXV bulb – Typical minimum for CME1056 • 0 to -5oF. • Low Charge - Remote – Will run until receiver is “dry” – Controller will shut unit down on max freeze time

  63. Slide 63: Remote Refrigeration

    Remote Refrigeration • To confirm low charge, recover and weigh OUT the charge • Headmaster will modulate when controlling pressure – Can only check at lower condensing temperatures < 70 - 75oF. – May not modulate at beginning of freeze - when heat load is high

  64. Slide 64: Freeze Cycle Data

    Freeze Cycle Data 50 60 T X V B u lb T em p s 45 40 50 35 S u ction P ressu re 30 40 25 T em p P S IG 20 30 15 10 20 5 0 10 -5 -1 0 0 T im e

  65. Slide 65: Refrigeration Diagnostics

    Refrigeration Diagnostics • TXV failure vs. Low Charge – High superheat is the symptom – Check by adding 10% of the charge • If no change, TXV is at fault • If superheat declines, charge is low and there is a leak • End of Freeze superheat maximums should be between 8oF. and 12oF.

  66. Slide 66: Compressor Diagnostics

    Compressor Diagnostics • Electrical – Starting • Check starting components & windings • Confirm capacitor PN & MFD • Check start relay – Use hard start kit – Impact shell – Overheating • TXV or Charge may be at fault

  67. Slide 67: Compressor Diagnostics

    Compressor Diagnostics • Confirm inefficient compressor – Process of elimination • TXV, Charge, Valves (water, hot gas) more likely to be at fault • Amp draw may be low if cannot pump to capacity • Normal amps: – 10, single phase; – 7 three phase

  68. Slide 68: Hot Gas Valve Diagnostics

    Hot Gas Valve Diagnostics • A hot gas valve is closed during a Freeze Cycle – If it leaks through, the heat from the discharge line will flow through it • Outlet will be hot - same as inlet – Frost at the evaporator connection is NORMAL • No frost also indicates a leak through

  69. Slide 69: Refrigeration Service

    Refrigeration Service R-404A Liquid Charge HFC Leak Detectors Weigh In Charge Evacuate to 300 microns Use Nitrogen Purge

  70. Slide 70: Summary

    Summary • CME1056 – Air Cooled – Water Cooled – Remote Air Cooled • CM3 technology • 30” wide • R-404A