Eaton Corporation, Plc · NYSE:ETN

Eaton — Technical Presentation (2014)

45 slides from Eaton's technical presentation, 2014

  1. Slide 1: New Automatic Test System AT-S+

    New Automatic Test System AT-S+ © 2014 Eaton, All Rights Reserved.

  2. Slide 2: More efficient Solutions for Emergency Lighting Systems

    More efficient Solutions for Emergency Lighting Systems Individual single luminaire monitoring of Central monitoring and control of self- up to 20 luminaires per circuit without contained luminaires including additional data line. automatic function- and duration test. Free programmability of switch

  3. Slide 3: System benefits

    System benefits Automatic test system AT-S+ for safety luminaries in projects with AC safety power source. • Savings on installation, battery maintenance, battery room • Minimum inspection effort via automatic luminaire monitoring • Reduced installation costs via programmable mixed operation • Witho

  4. Slide 4: Automatic test system AT-S+ for safety luminaries in projects with AC safety power source

    Automatic Test System AT-S+ Automatic test system AT-S+ for safety luminaries in projects with AC safety power source © 2014 Eaton, All Rights Reserved.

  5. Slide 5: AT-S+

    AT-S+ Important The new AT-S+ monitoring system is designed to monitor emergency AC lighting luminaires. The back-up power source (batteries, generator, 2nd grid) is not part of our scope of supply. The system integration of luminaires, mains power, second power source, system testing, etc. is the r

  6. Slide 6: Planning example for AT-S+ with only one riser

    Planning example for AT-S+ Planning example for AT-S+ with only one riser 3rd floor UVA UVA DLS DLS AT-S+ SU1 RV-E30 AT-S+ SU1 2nd floor UVA UVA DLS DLS AT-S+ SU1 RV-E30 AT-S+ SU1 1st floor UVA UVA DLS DLS AT-S+ SU1 RV-E30 AT-S+ SU1 cellar AT-S+ C4 AT-S+ C4 Operation Operation Not part of our Aggreg

  7. Slide 7: Planning example for AT-S+

    Planning example for AT-S+ 3rd floor UVA DLS 2nd floor UVA DLS 1st floor UVA DLS cellar Not part Operation of our business Aggregate on Failure HVS © 2014 Eaton, All Rights Reserved. 7 AT-S+ C30 Power supply E30 RS485 Terminator

  8. Slide 8: AT-S+ installation example

    AT-S+ installation 230/400V 50-60Hz example 14 1 2 1. AC power source for safety 15 3 service 20 3 2. AC power source, general 4 4 3. General lighting 5 5 4. Emergency lighting 5. DLS/3Ph/bus module 6. Connection terminals AT-S+ C30 7. Control unit CU S+ 6 16 8. DC/DC converter.2 17 18 9. AC supply

  9. Slide 9: Modules

    Automatic Test System AT-S+ Modules © 2014 Eaton, All Rights Reserved.

  10. Slide 10: Modules – Control unit CU S+

    Modules – Control unit CU S+ Control unit CU S+ • Graphic display • Foil keyboard • Two supplementary signal contacts • Access to servicing menu via special service SD card • Displaced SD card slot • Downwards-compatible to ST-S control unit • New LED / button designations • Web connection not direc

  11. Slide 11: Modules – Control unit CU S+

    Modules – Control unit CU S+ Technical data CU S+ Mechanic Dimensions (WxHxD) 110 x 170 x 155 mm Installation vertical RS485/CG-S Bus Degree of protection IP20 Output voltage ≤ 30 V Ambient temperature -5°C ... +55°C Polarity Independent Relative humidity 10 to 95 % no condensation Keyboard Inputs Z

  12. Slide 12: Modules – Control unit CU S+

    Modules – Control unit CU S+ 3 freely programmable Connection for blocking signal contacts switch and external 2 contacts permanently phase monitor programmed 3 buttons for: test (mains 3 freely assignable failure battery operation), function buttons function test, duration test Graphic display, 4 x

  13. Slide 13: Modules – Control unit CU S+

    Modules – Control unit CU S+ CU-S+ S3/S4: 24 V monitoring loop C0/14/12/24/22/34//32: external phase monitors 3 freely programmable S1/S2: External key-operated signal contacts switch, system blocked C1/44/54: 2 contacts permanently programmed © 2014 Eaton, All Rights Reserved. 13

  14. Slide 14: Modules – Control unit CU S+

    Modules – Control unit CU S+ Potential free relays 5 ralays, contacts: C0/14/12/24/22/34/32/ C1/44/54 © 2014 Eaton, All Rights Reserved. 14

  15. Slide 15: Modules – Control unit CU S+

    Modules – Control unit CU S+ 3 freely assignable function buttons for: • Block/release system • Manual reset • Function test without forward run. • Display error list • Switch on/off maintained mode • Switch on complete safety lighting (corridor lighting) © 2014 Eaton, All Rights Reserved. 15

  16. Slide 16: Modules – Control unit CU S+

    Modules – Control unit CU S+ LCD display, e.g. • Date/time • Manual reset • Test operation • Follow-on emergency light (residual time in mins.) • Luminaire error with location specification • UV-AV failure (location specification) • Error info/programming info © 2014 Eaton, All Rights Reserved. 16

  17. Slide 17: Modules – Control unit CU S+

    Modules – Control unit CU S+ Secure digital card: • Flexible data storage for system and log book configuration, e.g. regulations-compliant archiving of inspection book information over at least 4 years • System programming is possible on any PC via optional SD card reader and CEAG software. Texts c

  18. Slide 18: Modules – Control unit CU S+

    Modules – Control unit CU S+ CG-S bus: CGVision connection RS 485 bus: Connection of external modules, such as DLS, SOU, SU-S 24 V In/Out connections: Connection of 24 V supply of external modules, such as DLS, F3 remote display © 2014 Eaton, All Rights Reserved. 18

  19. Slide 19: Modules – Control unit CU S+

    Modules – Control unit CU S+ © 2014 Eaton, All Rights Reserved. 19

  20. Slide 20: Module – SU-S+ x A

    Module – SU-S+ 2 x 6 A Circuit module SU-S+ 2 x 6 A • Minimum inspection effort required due to automatic luminaire monitoring • Reduced installation costs via programmable mixed operation • No additional data lines to the luminaires © 2014 Eaton, All Rights Reserved. 20

  21. Slide 21: Module – SU-S+ x A

    Module – SU-S+ 2 x 6 A Logging on to the control unit via the search function CU S+ SU-S + 2 x 6 A (up to 40 modules) Neuron Assignment Installation location ID number CU CG-S control unit Building/ Room 1. In the "Circuit setup" SOU module Module support floor number submenu activate NID07 00 00C2

  22. Slide 22: Module – SU-S+ x A

    Module – SU-S+ 2 x 6 A Logging on to the control unit via the service pin SU-S + 2 x 6 A (max. 40 Module) 1. Press the service pin. CU S+ 2. Assign a module number (1 to 40) to the assembly. © 2014 Eaton, All Rights Reserved. 22

  23. Slide 23: Module – Status output

    Module – Status output Status output with flash code via service pin 1. To activate the flash code, press the service pin for at least 5 seconds. 2. Red LEDs alternately flashing indicates the display mode 1 , 2 . 3. After 1 second, the code will be displayed for circuit 1 1 4. Briefly pressing the

  24. Slide 24: Module – SU-S+ x A

    Module – SU-S+ 2 x 6 A Mains connection Connection for luminaire circuits LED circuit On Fuse LED fault, circuit 1 Circuit 1 LED fault, circuit 2 Service button Fuse Circuit 2 RS 485 bus connection © 2014 Eaton, All Rights Reserved. 24

  25. Slide 25: Module – SU-S+ x A

    Module – SU-S+ 2 x 6 A Technical data SU S+ 2 x 6 A Mechanic Dimensions (WxHxD) 107 x 90 x 58 mm Installation For top hat rail mounting Max. Inrush current 250 A/ms each circuit Permissible mains Degree of protection IP20 50 or 60 Hz frequency Climatic conditions Over all power loss 10 W (at 2 x 6A)

  26. Slide 26: Module – SOU-S+ x A

    Module – SOU-S+ 2 x 4 A SOU S+ 2 x 4 A • Area-specific installation enables electricity cost assignment per rental area • Reduced installation costs via programmable mixed operation • No additional data lines to the luminaires © 2014 Eaton, All Rights Reserved. 26

  27. Slide 27: Module – SOU-S+ x A

    Module – SOU-S+ 2 x 4 A Safety power source Rental Connection RS 485 bus 230 V AC current of end circuits connection feed 2x4A 230 V AV DIL switch Terminator Top hat rail housing, 10 subunits LED On, circuit 1 LED fault, circuit 1 End circuit fuse, circuit 1 LED On, circuit 2 (8AT 6.3 x 32) LED faul

  28. Slide 28: Module – SOU-S+ x A

    Module – SOU-S+ 2 x 4 A Technical Data SOU S+ 2 x 4 A Mechanic Dimensions (WxHxD) 178 x 108 x 60 mm Installation For top hat rail mounting Degree of protection IP20 Climatic conditions Maximum Inrush current 250 A/ms per circuit Permissible mains Ambient temperature -10 … +55° C 50 or 60 Hz frequenc

  29. Slide 29: Cabinet Variants

    Automatic Test System AT-S+ Cabinet Variants © 2014 Eaton, All Rights Reserved.

  30. Slide 30: Cabinet Variants

    Cabinet Variants View Designation AT-S+ C30 AT-S+ C16 AT-S+ C4 AT-S+ C0 Number of outgoing 6 6 6 - circuits Rated voltage 400/230 V 400/230 V 400/230 V 230 V Insulation class 1 1 1 1 Degree of protection IP21 IP21 IP21 IP54 Material/Design Sheet steel / Cabinet Sheet steel / Cabinet Sheet steel / Wa

  31. Slide 31: Cabinet Variants

    Cabinet Variants View Designation AT-S+ SU4 AT-S+ SU2 AT-S+ SOU2 AT-S+ SU1 AT-S+ SOU1 Order number 40071360504 40071360505 40071360508 40071360506 40071360509 Dimensions 590 x 300 x 130 460 x 300 x 130 590 x 300 x 130 460 x 300 x 130 460 x 300 x 130 (max., H x W x D) Control unit: CU S+ - - - - - DC

  32. Slide 32: Cabinet Variants

    Cabinet Variants View Designation AT-S+ SU4 AT-S+ SU2 AT-S+ SOU2 AT-S+ SU1 AT-S+ SOU1 Number of outgoing - - - - - circuits Rated voltage 230 V 230 V 230 V Insulation class 2 2 2 2 2 Degree of protection IP65 IP65 IP65 IP65 IP65 Plastic / Small Plastic / Small Plastic / Small Plastic / Small Plastic

  33. Slide 33: AT-S+ C30 cabinet design

    AT-S+ C30 cabinet design Cable infeed from above Triple-deck tension spring installation terminal with neutral wire disconnect terminal Lütze mounting system Control unit CU S+ DC/DC converter.2 AC module Circuit switching modules 30 x SU-S+ 2 x 6 A Fuse circuit breaker D02 25 A per field 6-fold mai

  34. Slide 34: AT-S+ C16 cabinet design

    AT-S+ C16 cabinet design Cable infeed from above Triple-deck tension spring installation terminal with neutral wire disconnect terminal Control unit CU S+ Lütze mounting system DC/DC converter.2 AC module Circuit switching modules 16 x SU-S+ 2 x 6 A Fuse circuit breaker D02 25 A per field Fuse circu

  35. Slide 35: AT-S+ C4 cabinet design

    AT-S+ C4 cabinet design Cable infeed from above 6-fold mains distribution box D02 16 A Fuse circuit breaker NH 000 Control unit CU S+ Triple-deck tension spring installation terminal with neutral wire disconnect terminal DC/DC converter.2 AC module Circuit switching modules 4x SU-S+ 2 x 6 A © 2014 E

  36. Slide 36: AT-S+ C0 cabinet design

    AT-S+ C0 cabinet design Cable infeed from above Triple-deck tension spring installation terminal with neutral wire disconnect terminal 1. Control unit CU S+ DC/DC converter.2 AC module 2. Control unit CU S+ (optional) DC/DC converter.2 (optional) AC module (optional) © 2014 Eaton, All Rights Reserve

  37. Slide 37: AT-S+ SOU2 cabinet design

    AT-S+ SOU2 cabinet design Cable infeed from above Two feeders (rental Type plate, current and power source quick start guide for safety service) End circuit terminals RS 485 bus connection Sighting window Circuit switching module SOU S+ 2 x 4 A Circuit designation field Cable infeed from below © 201

  38. Slide 38: AT-S+ SOU1 cabinet design

    AT-S+ SOU1 cabinet design Cable infeed from above Two feeders (rental current and power source for safety service) Type plate, quick start guide End circuit terminals RS 485 bus connection Circuit switching module Sighting window SOU S+ 2 x 4 A Circuit designation field Cable infeed from below © 201

  39. Slide 39: AT-S+ SU4 cabinet design

    AT-S + SU4 cabinet design Cable infeed from above Type plate, Power source feed quick start guide for safety service End circuit terminals RS 485 bus connection Sighting window Circuit switching module SU S+ 2 x 6 A Circuit designation field Cable infeed from below © 2014 Eaton, All Rights Reserved.

  40. Slide 40: AT-S+ SU2 cabinet design

    AT-S + SU2 cabinet design Cable infeed from above Power source feed for safety service Type plate, quick start guide End circuit terminals RS 485 bus connection Circuit switching module Sighting window SU S+ 2 x 6 A Circuit designation field Cable infeed from below © 2014 Eaton, All Rights Reserved.

  41. Slide 41: AT-S+ SU1 cabinet design

    AT-S+ SU1 cabinet design Cable infeed from above Power source feed for safety service Type plate, quick start guide End circuit terminals RS 485 bus connection Circuit switching module Sighting window SU S+ 2 x 4 A Circuit designation field Cable infeed from below © 2014 Eaton, All Rights Reserved.

  42. Slide 42: Bus Systems

    Automatic Test System AT-S+ Bus Systems RS485 Bus © 2014 Eaton, All Rights Reserved.

  43. Slide 43: Bus Systems

    Bus Systems CU S+ SOU S+ 2 x 4 A SU S+ 2 x 6 A DLS 3-Ph Bus Modul (together max. 40 modules) (max. 25 modules) 2 Terminator Terminator 120  120  2 1 Max. Buslänge 1200 m mit JY(ST)Y 4 x 2 x 0,8 mm RS485 Bus RS 485 bus Notes: Bus topology: linear, double terminated (no branch cables permissible). R

  44. Slide 44: Bus Systems

    Bus Systems SU S+ DLS SOU S+ DLS RS485 Bus RS485 Bus CG-S bus (FTT10A) • CG Controller ZB-S • CG Vision AT-S+ C0 © 2014 Eaton, All Rights Reserved. 44

  45. Slide 45: CEAG Notlichtsysteme GmbH, Senator-Schwartz-Ring 26, D-59494 Soest

    CEAG Notlichtsysteme GmbH, Senator-Schwartz-Ring 26, D-59494 Soest www.ceag.de © 2014 Eaton, All Rights Reserved. 45