  1. Slide 1: Relay retrofit program: General presentation

    — ABB DISTRIBUTION SOLUTIONS, EP SERVICE Relay retrofit program General presentation 1MRS757635 D

  2. Slide 2: Content

    — Relay retrofit program Content Life cycle management Overview Replacement IEDs, dedicated tools and accessories Existing relays and selected replacement IEDs Retrofit project phases and dedicated tools Engineering Installation and mounting Testing Documentation and training Added value for the cus

  3. Slide 3: Life cycle management

    — Relay retrofit program Life cycle management ABB’s life cycle extension initiative targets to support the life cycle management (LCM) of utility and industrial power distribution systems One strategic consideration of the LCM of a power system is to extend the life cycle of a switchgear panel thro

  4. Slide 4: Overview

    — Relay retrofit program Overview Relay retrofit program is based on – Using IEDs belonging to the Relion® product family as replacement devices – Pre-designed installation accessories – Using a dedicated IED Migration Support Tool (MST) This carefully engineered program provides you with – A contro

  5. Slide 5: Variety of solutions to extend the installation's lifetime

    — Relay retrofit program Variety of solutions to extend the installation’s lifetime ABB has a variety of solutions to extend the complete installation’s lifetime via offering the most suitable protection system refurbishment option. Every case has its own characteristics, which must be considered. H

  6. Slide 6: Replacement IEDs, tools and accessories

    — Relay retrofit program Replacement IEDs, tools and accessories The Relay retrofit program for the selected relays consists of the following: – 615 series protection and control IEDs – IED Migration Support Tool (MST) – Relion Test Box RTB615 with masking plates – Replacement IED test templates – W

  7. Slide 7: Existing relays and selected replacement IEDs

    — Relay retrofit program Existing relays and selected replacement IEDs Relay type(s) to be retrofitted New replacement IED Ordering code #BMAAC##########1E MCX 912 REM615 standard configuration “A” #BMAAG##########1E1 #BMAAC##########1E MCX 913 REM615 standard configuration “A” #BMAAG##########1E1 S

  8. Slide 8: Retrofit project phases and dedicated tools

    — Relay retrofit program Retrofit project phases and dedicated tools Retrofit project phases Dedicated tools and accessories IED Migration Support Tool Engineering Documentation Cutting tool Cover plates Mounting and Installation Wire markings and wiring harness Documentation Relion Test Box RTB615

  9. Slide 9: Retrofit project phases: Engineering

    — Retrofit project phases Engineering

  10. Slide 10: IED Migration Support Tool (MST)

    — Engineering IED Migration Support Tool (MST) MST offers you an easy, fast and efficient way to process the parameters of the existing relay and map them to the selected replacement IED. MST also defines the configuration of the IED based on functionality of the existing relay. As a result of the m

  11. Slide 11: Migration example of SPAJ C to REF615

    — Engineering Migration example of SPAJ 140 C to REF615 The MST runs on PCM600 MST PCM600 PCM600. It is delivered in a retrofit connectivity Retrofit New IED package. IED REF615 MST utilizes the Switchgear x Switchgear x information provided by Bay 1 Mapping REF615, Bay 1 the retrofit migration Migr

  12. Slide 12: Migration Support Tool tutorial

    — Engineering Migration Support Tool tutorial The Relay Retrofit Program Migration Support Tool tutorial is available on the program’s web page. The tutorial provides an overview to migrating an existing relay using the IED Migration Support Tool. September 27, Slide 12 2018

  13. Slide 13: Retrofit project phases: Installation and mounting

    — Retrofit project phases Installation and mounting

  14. Slide 14: Wire markings and wiring harness

    — Installation and mounting Wire markings and wiring harness You can significantly reduce the time and effort needed for planning, preparation and implementation thanks to the ready-made wire markings and wiring harness. Wire markings are provided as complete sets. The sets correspond to the termina

  15. Slide 15: Cutting tool

    — Installation and mounting Cutting tool The cutting tool is a dedicated handheld battery-driven device for machining the existing panel cutout. No need for time consuming measurements or additional panel surface protection. The tool allows you to cut a panel metal sheet with a thickness of up to 2.

  16. Slide 16: Cutting tool kit

    — Installation and mounting Cutting tool The tool is delivered in a cutting tool kit. The cutting tool kit is a dedicated plastic case containing – A power unit – SPACOM1 or MCX2 cutting head – Two batteries and – A battery charger September 27, Slide 16 2018

  17. Slide 17: Cover plates

    — Installation and mounting Cover plates If the existing panel cut-out is larger than that of the replacement IED, or if it has a different format, you can use the predesigned cover plate for adjusting the cut-out size. Cover plates enable quick and easy mounting of the replacement IEDs. September 2

  18. Slide 18: Retrofit project phases: Testing

    — Retrofit project phases Testing

  19. Slide 19: Relion Test Box RTB615

    — Testing Relion Test Box RTB615 RTB615 is a test box for 615 series’ plug-in units1 RTB615 provides auxiliary power for the plug-in unit and an interface for a secondary test device, such as Omicron. RTB615 is equipped with an IED type-specific masking plate leaving just those terminals accessible,

  20. Slide 20: Replacement IED test workflow

    — Testing Replacement IED test workflow The replacement IED test templates include test rules used by the PCM600 Omicron Test Universe for testing replacement IEDs after configuration and parameter migration. Parameter The test template specifies the content and format of the test setting tool repor

  21. Slide 21: Retrofit project phases: Documentation and training

    — Retrofit project phases Documentation and training

  22. Slide 22: Program web page

    — Relay retrofit program Program web page Link to the program page September 27, Slide 22 2018

  23. Slide 23: Training

    — Relay retrofit program Training A one-day classroom training course – Introduces the tools and equipment used in the program – Provides practical information on how to effectively carry out relay retrofit projects The course code is P271. For further information visit the training web pages. Septe

  24. Slide 24: Added value and conclusions

    — Retrofit project phases Added value and conclusions

  25. Slide 25: Added value for the customer

    — Relay retrofit program Added value for the customer Controlled and repeatable procedure for replacing existing protection relays with modern IEDs allows you to – Improve the quality of the overall project – Accurately plan the project budget and time schedule – Quickly and efficiently carry out th

  26. Slide 26: Added value for the customer

    — Relay retrofit program Added value for the customer The program provides a controlled and repeatable procedure for replacing the existing protection relays with modern IEDs. The program stands for constant quality, time saving and repeatable procedures. Migration support tool (MST) for the migrati

  27. Slide 27: AL GD ED

    AL GD ED FADD ED

ABB — Technical Presentation (September 2018) on 6ix